Tianjin Feiya Wire&Cable Co.,Ltd

Product Detail
Medium Voltage Power Cables Water Blocked P2 or P2/P9 RFOU/TFOU 3.6/6KV
Detail

Applications

These cables are partially water blocked, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

Standards

  • IEC 60092-353IEC 60092-351
    IEC 60092-359IEC 60332-1
    IEC 60332-3-22IEC 60754-1,2
    IEC 61034-1,2NEK 606:2004
    VG 95218 part 29?

Water Blocked P2 or P2/P9 RFOU/TFOU 3.6/6KV

Construction

  • Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.
    Conductor Screen: Semi conducting material.
    Insulation: Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
    Insulation Screen: Semi conducting material and tinned copper wire braid.
    Filler: Water blocking fillers, if required.
    Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
    Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
    Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
    Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P2), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P2/P9), coloured red.
    Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.

Electrical Characteristics

  • Nominal Cross Section Areamm2162535507095120
    Nominal Conductor Diametermm5.16.57.48.710.312.213.8
    Maximum DC Resistant@20˚CO/km1.160.7340.5290.3910.270.1950.154
    Continuous Current Rating@45˚C1 CoreA96127157196242293339
    Continuous Current Rating@45˚C3 CoreA6789110137169205237
    Short Circuit Current 1sA2290358050107150100201359017170
    Operating VoltageKV3.6/63.6/63.6/63.6/63.6/63.6/63.6/6

    Nominal Cross Section Areamm2150185240300400500630
    Nominal Conductor Diametermm15.117.019.621.924.627.632.5
    Maximum DC Resistant@20˚CO/km0.1260.10.07620.06070.04750.03690.0286
    Continuous Current Rating@45˚C1 CoreA389444522601690780890
    Continuous Current Rating@45˚C3 CoreA272311365421483546623
    Short Circuit Current 1sA21460264703434042930572307154090140
    Operating VoltageKV3.6/63.6/63.6/63.6/63.6/63.6/63.6/6

Ambient Temperature Correction Factors

  • Ambient Temperature Correction Factors35404550556065707580
    Rating Factor1.11.051.00.940.880.820.740.670.580.47

Mechanical and Thermal Properties

Bending Radius :15×OD (during installation); 9×OD (fixed installed).
Temperature Range : -20˚C ~ +90˚C.

Dimensions and Weight

Construction No. of cores×Cross section

(mm2)

Nominal Insulation Thickness

mm

Nominal BeddingThickness

mm

NominalInner Sheath Thickness

mm

NominalOuter Sheath Thickness

mm



Nominal Overall
Diameter

mm

Nominal Weight

kg/km

1×162.51.41.1124.8±2819
1×252.51.51.11.226.4±21071
1×352.51.51.21.227.5±21213
1×502.51.61.21.228.7±21386
1×702.51.61.31.230.6±21675
1×952.51.71.31.432.8±22000
1×1202.51.81.41.434.6±22347
1×1502.51.81.41.436.3±22678
1×1852.51.91.51.438.0±23166
1×2402.621.51.642.0±23911
1×3002.82.11.61.645.5±24856
1×40032.21.71.649.8±25691
1×5003.22.41.81.654.0±26941
1×6303.22.51.91.658.3±28579
3×162.52.21.6146.9±23077
3×252.52.31.71.247.8±23560
3×352.52.41.81.250.0±24011
3×502.52.51.91.253.3±24720
3×702.52.721.257.2±25864
3×952.52.82.11.461.7±27103
3×1202.532.21.466.3±28573
3×1502.53.12.31.470.2±29970
3×1852.53.32.41.478.6±211193
3×2402.63.52.51.685.5±212243
3×3002.83.82.71.692.5±213587


CONTACT US Tel: 0086-22-83965099
Mobile: 0086 15510897703
CONTACT EMAIL amy@cn-fengda.com
Login
Login
Login by:
leave a message