Applications
These heavy duty cables are designed for applications such as longwall shearers, continuous miners and mobile equipment such as shovels, dredges and drills.
Standards
ICEA S-75-381/NEMA WC 58
ASTM B 172
ASTM B 33
CAN/CSA-C22.2 No.96
Construction
Conductors: Stranded annealed tinned copper conductor.
Conductor Shield:Semi-conducting layer.
Insulation:EPR.
Insulation Shield:Non-conducting tape + Tinned copper/textile braid.
Ground Check Conductor:Tinned copper with a yellow polypropylene insulation.
Grounding Conductor:Tinned copper conductor.
Sheath: Reinforced extra-heavy-duty Chlorinated Polyethylene(CPE), black. Other sheath materials can be offered upon request.
Options:
Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.
Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.
Mechanical and Thermal Properties
Dimensions and Weight:
CONSTRUCTION | NO. OF STRANDS | GROUNDING CONDUCTOR SIZE | GROUND CHECK CONDUCTOR SIZE | NOMINAL INSULATION THICKNESS | NOMINAL SHEATH THICKNESS | NOMINAL SHEATH THICKNESS | NOMINAL WEIGHT | AMPACITY |
---|
NO. OF CORES×AWG/KCMIL | - | AWG/KCMIL | AWG/KCMIL | INCH | MM | INCH | MM | INCH | MM | LBS/KFT | KG/KM | A |
---|
3×1 | 259 | 5 | 8 | 0.260 | 6.6 | 0.265 | 6.7 | 2.95 | 74.9 | 5290 | 7872 | 191 |
3×1/0 | 259 | 4 | 8 | 0.260 | 6.6 | 0.265 | 6.7 | 3.05 | 77.5 | 5800 | 8631 | 218 |
3×2/0 | 329 | 3 | 8 | 0.260 | 6.6 | 0.280 | 7.1 | 3.20 | 81.3 | 6515 | 9695 | 249 |
3×3/0 | 413 | 2 | 8 | 0.260 | 6.6 | 0.280 | 7.1 | 3.33 | 84.6 | 7215 | 10737 | 286 |
3×4/0 | 532 | 1 | 8 | 0.260 | 6.6 | 0.295 | 7.5 | 3.50 | 88.9 | 8250 | 12277 | 327 |
Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.