Applications
These cables are designed for connections between units of mine distribution systems, suitable forinstalled in duct, conduit or open air and for direct burial in wet and dry locations.
Standards
ICEA S-75-381/NEMA WC 58
ASTM B-8
CAN/CSA-C22.2 No.96
Construction
Conductors: Stranded annealed bare copper conductor.
Conductor Shield:Semi-conducting layer.
Insulation:EPR.
Insulation Shield:Semi-conducting layer + copper tape.
Ground Check Conductor:Copper conductor with a yellow polypropylene insulation.
Grounding Conductor:Tinned copper conductor.
Sheath: Chlorinated Polyethylene(CPE), black. Other sheath materials can be offered as an option.
Options:Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.
Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.
Mechanical and Thermal Properties
Dimensions and Weight:
CONSTRUCTION | NO. OF STRANDS | GROUNDING CONDUCTOR SIZE | GROUND CHECKCONDUCTOR SIZE | NOMINAL INSULATION THICKNESS | NOMINAL SHEATH THICKNESS | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT | AMPACITY |
---|
NO. OF CORES×AWG/KCMIL | - | AWG/KCMIL | AWG/KCMIL | INCH | MM | INCH | MM | INCH | MM | LBS/KFT | KG/KM | A |
---|
3×6 | 7 | 10 | 8 | 0.09 | 2.3 | 0.11 | 2.8 | 1.30 | 33.0 | 1060 | 1577 | 93 |
3×4 | 7 | 8 | 8 | 0.09 | 2.3 | 0.11 | 2.8 | 1.41 | 35.8 | 1441 | 2144 | 122 |
3×2 | 7 | 6 | 8 | 0.09 | 2.3 | 0.11 | 2.8 | 1.47 | 37.3 | 1827 | 2718 | 159 |
3×1 | 19 | 5 | 8 | 0.09 | 2.3 | 0.11 | 2.8 | 1.54 | 39.1 | 2168 | 3226 | 184 |
3×1/0 | 19 | 4 | 8 | 0.09 | 2.3 | 0.11 | 2.8 | 1.63 | 41.4 | 2602 | 3871 | 211 |
3×2/0 | 19 | 3 | 8 | 0.09 | 2.3 | 0.11 | 2.8 | 1.72 | 43.7 | 3010 | 4478 | 243 |
3×3/0 | 19 | 2 | 8 | 0.09 | 2.3 | 0.14 | 3.6 | 1.89 | 48.0 | 3265 | 4859 | 279 |
3×4/0 | 19 | 1 | 8 | 0.09 | 2.3 | 0.14 | 3.6 | 2.01 | 51.0 | 4190 | 6234 | 321 |
3×250 | 37 | 1/0 | 8 | 0.09 | 2.3 | 0.14 | 3.6 | 2.10 | 53.3 | 4825 | 7179 | 355 |
3×350 | 37 | 2/0 | 8 | 0.09 | 2.3 | 0.14 | 3.6 | 2.31 | 58.7 | 6062 | 9019 | 435 |
3×500 | 37 | 4/0 | 8 | 0.09 | 2.3 | 0.14 | 3.6 | 2.59 | 65.8 | 8427 | 12538 | 536 |
Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.