300/500V PVC Insulated, PVC Sheathed Power Cables (2-5 Cores)
Detail

300/500V PVC Insulated, PVC Sheathed Power Cables (2-5 Cores)

FGD200 05VV-K (CU/PVC/PVC 300/500V Class 5)

BS Code: 3182Y/3183Y/3184Y/3185Y

HAR Code: H05VV-F

Application

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.

Standards

  • Basic design to BS EN 50525-2-11(formerly BS 6500)

Fire Performance

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2

Voltage Rating

300/500V

Cable Construction

PVC Insulated, PVC Sheathed Power CablesPVC Sheathed Power Cables
ConductorFlexible copper wire according to EN 60228 class 5.
InsulationPVC type TI 2 according to EN 50363-3.
FillingFor circular cable having two cores, the space between the cores shall be filled either by separate fillers or by the sheath filling the interstices. For circular cables with three, four or five cores, a centre filler may be used.
Outer SheathPVC type TM 2 according to EN 50363-4-1. A tape may be applied around the core assembly before application of the sheath.
Sheath OptionUV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

Colour Code

Insulation Colour

Cables and cords with a green-and-yellow cores
No. of coresColour of coresb
ProtectiveLive
3 CoresYellow/GreenBlueBrown

4 CoresYellow/Green-BrownBlackGrey
4 CoresaYellow/GreenBlueBrownBlack
5 CoresYellow/GreenBlueBrownBlackGrey
a For certain applications only.
b In this table an uninsulated concentric conductor, such as a metallic sheath, armour or screen wire, is not regarded as a core. A concentric conductor is identified by its position and, therefore, need not be identified by colour.
Cables and cords without a green-and-yellow cores
No. of coresColour of coresb
2 CoresBlueBrown


3 Cores-BrownBlackGrey
3 CoresaBlueBrownBlack

4 CoresBlueBrownBlackGrey
5 CoresBlueBrownBlackGreyBlack
a For certain applications only.
b In this table an uninsulated concentric conductor, such as a metallic sheath, armour or screen wire, is not regarded as a core. A concentric conductor is identified by its position and, therefore, need not be identified by colour.

Sheath Colour: Black (other colors upon request)

Physical And Thermal Properties

Maximum temperature range during operation (PVC)60°C
Maximum short circuit temperature (5 Seconds)150°C
Minimum bending radiusUp to 12mm²: 3 x overall diameter

Above 12mm²: 4 x overall diameter

Construction Parameters

No. of Core X Cross SectionFGD200 05VV-K
Nominal Insulation ThicknessNominal Sheath ThicknessMaximum Overall DiameterApprox. Weight
Noxmm2mmmmmmkg/km
2x0.750.60.87.257
2x1.00.60.87.565
2x1.50.70.88.687
2x2.50.81.010.6134
2x40.81.112.1174
3x0.750.60.87.668
3x1.00.60.88.079
3x1.50.70.99.4111
3x2.50.81.111.4169
3x40.81.213.1233
4x0.750.60.88.384
4x1.00.60.99.0101
4x1.50.71.010.5142
4x2.50.81.112.5211
4x40.81.214.3292
5x0.750.60.99.3106
5x1.00.60.99.8123
5x1.50.71.111.6176
5x2.50.81.213.9262
5x40.81.416.1369

Electrical Properties

Current-Carrying Capacities (Amp) according to BS7671:2008 table 4F3A

Conductor cross-sectional areaSingle-phase a.c.Three-phase a.c.
mm2AA
0.533
0.7566
1.01010
1.51616
2.52520
43225

Voltage Drop (Per Amp Per Meter) according to BS7671:2008 table 4F3B

Conductor cross-sectional aread.c. or single-phase a.c.Three-phase a.c.
mm2mV/A/mmV/A/m
0.59380
0.756254
1.04640
1.53227
2.51916
41210