Application
These cables are used as supply or interconnecting cables for measuring, controlling and regulating for light and medium mechanical stresses.
Standards
Construction
Conductor | Stranded bare copper, class 5/class 6 according to IEC 60228 |
Insulation | PVC Type YI 4 |
Sheath | PVC oil resistant Type YM 5 |
Technical Data
Rated Voltage Uo/U (Um) | 300/500 V |
Operating Temperatures | flexing: -15℃~+80℃; fixed: -40℃~+80℃ |
Minimum Bending Radius | flexing: 10×OD; fixed: 6×OD |
Flame Retardant | IEC 60332-1 |
Oil Resistant | Yes |
Ozone Resistant | Yes |
Silicone Free | Yes |
Dimensions and Weight
CONSTRUCTION | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT |
---|
NO. OF CORES×MM2 | MM | KG/KM |
---|
3G0.75 | 6.5 | 57 |
4G0.75 | 7.0 | 70 |
5G0.75 | 7.8 | 89 |
7G0.75 | 9.4 | 130 |
12G0.75 | 11.5 | 174 |
18G0.75 | 13.8 | 259 |
25G0.75 | 16.8 | 362 |
41G0.75 | 21.5 | 602 |
50G0.75 | 23.6 | 723 |
2×1 | 6.2 | 54 |
3G1 | 6.7 | 66 |
4G1 | 7.5 | 82 |
5G1 | 8.0 | 105 |
7G1 | 9.6 | 149 |
12G1 | 12.3 | 210 |
14G1 | 13.9 | 267 |
18G1 | 14.4 | 302 |
25G1 | 17.5 | 418 |
34G1 | 21.4 | 622 |
2×1.5 | 7.7 | 75 |
3G1.5 | 7.9 | 93 |
4G1.5 | 8.9 | 117 |
5G1.5 | 10.3 | 143 |
7G1.5 | 11.9 | 220 |
12G1.5 | 14.3 | 292 |
18G1.5 | 17.2 | 435 |
25G1.5 | 21.2 | 620 |
34G1.5 | 24.5 | 842 |
50G1.5 | 30.3 | 1305 |
3G2.5 | 9.4 | 144 |
4G2.5 | 10.8 | 180 |
5G2.5 | 11.8 | 229 |
7G2.5 | 14.0 | 300 |
12G2.5 | 17.3 | 453 |
18G2.5 | 20.5 | 684 |
25G2.5 | 25.5 | 943 |
G: with green-yellow earth core
×: without green-yellow earth core