Water Blocked S16 BFOU-HCF(c) 250 V
Detail

Applications

  • These cables are partially water blocked, fire resistant, flame retardant, low smoke and halogen free, used for emergency instrumentation, communication, control and alarm systems that need to be operational during a 1100°C hydrocarbon fire.

Standards

  • IEC 60092-376IEC 60092-351
    IEC 60092-359IEC 60332-1
    IEC 60332-3-22IEC 60754-1,2
    IEC 61034-1,2NEK 606:2004
    IEC 60331-21VG 95218 part 29?

Water Blocked S16 BFOU-HCF(c) 250 V

Construction

  • Conductors: Circular tinned stranded copper wire to IEC 60228 class 2.
    Insulation: Mica tape + Halogen free EPR compound.
    Twinning: Colour coded cores twisted together.
    Collective Shielding: Pairs/triples are layed up and collectively screened by copper backed polyester tape in contact with a stranded tinned copper drain wire. Pairs/triples are numbered with numbered tape or by numbers printed directly on the insulated conductors.
    Filler: Water blocking fillers, if required.
    Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
    Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
    Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
    Inner Sheath: Halogen free thermosetting compound, SHF2.
    HC-fire protection: Extruded thermoplastic fire protection compound.
    Taping: Lapped glass fibre tape.
    Outer Sheath 1: Flame retardant halogen-free thermoplastic compound, type SHF1, coloured grey (blue for intrinsically safe).
    Outer Sheath 2: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.

Electrical Characteristics

  • Nominal Cross Section Areamm21.5
    Nominal Conductor Diametermm1.6
    Maximum Resistant@20˚CO/km12.9
    Mutual CapacitancenF/km85
    Nominal Inductance@1KHzMH/km0.667
    Operating VoltageV250

Mechanical and Thermal Properties

  • Bending Radius : 20×OD (during installation); 12×OD (fixed installed).

  • Temperature Range : -20˚C ~ +90˚C.

Dimensions and Weight

Construction
No. of elements×No. of cores in element×Cross section

(mm2)

Nominal
Insulation Thickness

mm

Nominal
Diameter Over Bedding

mm

Nominal
Diameter Over Inner Sheath

mm

Nominal Overall
Diameter

mm

Nominal Weight

kg/km

2×2×1.50.71316.446.5±22520
4×2×1.50.71519.948.5±22783
8×2×1.50.720.525.355.0±23749
12×2×1.50.723.529.659.0±24368