NEK606 Marine Cables Water Blocked P34 BFOU-HCF 0.6/1 kV
Detail
Applications
These cables are partially water blocked, fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100°C hydrocarbon fire.
Standards
IEC 60092-353
IEC 60092-351
IEC 60092-359
IEC 60332-1
IEC 60332-3-22
IEC 60754-1,2
IEC 61034-1,2
NEK 606:2004
VG 95218 part 29
Construction
Conductors: Tinned annealed stranded compacted copper to IEC 60228 class 2. Insulation: Mica tape + Halogen free EPR/XLPE. Filler: Water blocking fillers, if required. Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required. Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required. Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness. Inner Sheath: Halogen free thermosetting compound, SHF2. HC-fire protection: Extruded thermoplastic fire protection compound. Taping: Lapped glass fibre tape. Outer Sheath 1: Flame retardant halogen-free thermoplastic compound, SHF1, coloured black.
Outer Sheath 2: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
Electrical Characteristics
Nominal Cross Section Area
mm2
1.5
2.5
4
6
16
35
Nominal Conductor Diameter
mm
1.6
2.1
2.6
3.2
5.1
7.4
Maximum DC Resistant@20˚C
O/km
12.2
7.56
4.7
3.11
1.16
0.529
Continuous Current Rating@45˚C1 Core
A
23
30
40
52
96
157
Continuous Current Rating@45˚C2 Core
A
20
26
34
44
82
133
Continuous Current Rating@45˚C3&4 Core
A
16
21
28
36
67
110
Short Circuit Current 1s
A
210
360
570
860
2290
5010
Operating Voltage
KV
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
Nominal Cross Section Area
mm2
50
70
95
120
150
185
240
300
Nominal Conductor Diameter
mm
8.7
10.3
12.2
13.8
15.1
17.0
19.6
21.9
Maximum DC Resistant@20˚C
O/km
0.391
0.27
0.195
0.154
0.126
0.1
0.0762
0.0607
Continuous Current Rating@45˚C1 Core
A
196
242
293
339
389
444
522
601
Continuous Current Rating@45˚C2 Core
A
167
206
249
288
331
444
444
511
Continuous Current Rating@45˚C3&4 Core
A
137
169
205
237
272
311
365
421
Short Circuit Current 1s
A
7150
10020
13590
17170
21460
26470
34340
42930
Operating Voltage
KV
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN=I1/ 3v N ), I1= Current rating for 1-core, N = Number of cores.