450/750V XLPE Insulated, LSZH Sheathed, Screened Power Cables (multicore)
Detail
450/750V XLPE Insulated, LSZH Sheathed, Screened Power Cables (multicore)
FTX200 07RCZ1-R (CU/XLPE/CUTO/LSZH 450/750V Class 2)
APPLICATION The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS Basic design to BS 7211; IEC 60502-1
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
minimum Smoke Emission
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases
NES 02-713; NF C 20-454
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING 450/750V
CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2. Insulation: Extruded cross-linked XLPE compound. Filler, binder (if any): PP, PET, LSZH Overall Screen: Copper tape Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE Insulation colour as per bs7671
with earth conductor
without earth conductor
2Cores
-
Brown,Blue
3Cores
Yellow/Green,Brown,Blue
Brown,Gray,Black
4Cores
Yellow/Green,Brown,Gray,Black
Brown,Gray,Black,Blue
5Cores
Yellow/Green,Brown,Gray,Black,Blue
Brown,Gray,Black,Blue,Black
above 5 Cores
Yellow/Green,Black Numbered
Black Numbered
sheath colour: Black
Physical AND THERMAL PROPERTIES Temperature range during operation: Max.90°C for XLPE 250°C in short-circuit for 5s max. Minimum bending radius: 8 x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor
FTx200 07RcZ1-R
No. of Core X Cross Section
No./ Nominal Diameter of Strands
Nominal Overall Diameter Conductor
Nominal Insulation Thickness
Nominal Copper Tape Thickness
Nominal Sheath Thickness
Nominal Overall Diameter
max.DC resistance of conductor @20°C
Approx. Weight
Noxmm2
No./mm
mm
mm
mm
mm
mm
Ω/km
kg/km
7x1.0
7/0.44
1.32
0.7
0.1
1.3
13.9
18.1
309
7x1.5
7/0.53
1.59
0.7
0.1
1.4
14.8
12.1
366
7x2.5
7/0.44
2.01
0.7
0.1
1.4
16.2
7.41
468
12x1.5
7/0.53
1.59
0.7
0.1
1.5
18.9
12.1
560
12x2.5
7/0.67
2.01
0.7
0.1
1.5
20.8
7.41
727
19x1.5
7/0.53
1.59
0.7
0.1
1.6
21.9
12.1
786
19x2.5
7/0.67
2.01
0.7
0.1
1.6
24.2
7.41
1,037
Electrical PROPERTIES Conductor Operating Temperature : 90°C Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor cross- sectional area
Reference method 4 (enclosed in conduit in thermally insulating wall etc)
Reference method 3 (enclosed in conduit on a wall or in trunking etc)
Reference method 1 (clipped direct)
Reference method 11 (on a perforated cable tray, horizontal or vertical)
Reference method 12 (free air)
Horizontal flat spaced
Vertical flat spaced
Trefoil
2 cables, single- phase a.c. or d.c.
3 or 4 cables, 3-phase a.c.
2 cables, single- phase a.c. or d.c
3 or 4 cables, 3-phase a.c.
2 cables, single- phase a.c. or d.c. flat and touching
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or flat and touching
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or 3 c ables three phase
2 cables, single- phase a.c. or d.c. or 3 cables three phase
3 cables, trefoil 3-phase a.c.
1
2
3
4
5
6
7
8
9
10
11
12
mm2
A
A
A
A
A
A
A
A
A
A
A
1.0
13
-
-
-
15
-
-
-
-
-
-
1.5
18
17
22
19
25
23
-
-
-
-
-
2.5
24
23
30
26
34
31
-
-
-
-
-
4
33
30
40
35
46
41
-
-
-
-
-
Voltage Drop (Per Amp Per Meter)
Nominal Cross Section Area
2 cables d.c.
2 cables, single-phase a.c.
3 or 4 cables, 3-phase a.c.
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)
Ref. Methods 1 and 11 (clipped direct or on trays touching)
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)