FTX400 1RZ1MZ1-R (CU/XLPE/LSZH/DSTA/LSZH 600/1000V Class 2)
APPLICATION The cables is mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS Basic design to IEC 60502-1
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
minimum Smoke Emission
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases
NES 02-713; NF C 20-454
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING 600/1000V
CABLE CONSTRUCTION Conductor: Plain annealed copper wire, normal stranded or compact stranded according to IEC(EN) 60228 class 2. Insulation: Extruded cross-linked XLPE compound. Filler, binder and inner covering: PP, PET, LSZH Armouring: Double steel tape Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE Insulation Colour as per BS7671
with earth conductor
without earth conductor
2Cores
-
Brown,Blue
3Cores
Yellow/Green,Brown,Blue
Brown,Gray,Black
4Cores
Yellow/Green,Brown,Gray,Black
Brown,Gray,Black,Blue
5Cores
Yellow/Green,Brown,Gray,Black,Blue
Brown,Gray,Black,Blue,Black
above 5 Cores
Yellow/Green,Black Numbered
Black Numbered
Sheath Colour: Black
Physical AND THERMAL PROPERTIES Temperature range during operation: Max.90°C for XLPE 250°C in short-circuit for 5s max. Minimum bending radius: 10x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor
FTX400 1RZ1MZ1-R
No. of Core X Cross Section
Phases
Neutral
Nominal Diameter Overall Conducrtor
Nominal Insulation Thickness
Nominal Steel Tape Thickness
Nominal Sheath Thickness
Nominal Overall Diatemer
Approx. Weight
No./ Nominal Diameter of Strands
No./ Nominal Diameter of Strands
Pha.
Neu.
Pha.
Neu.
mm2
No/mm
No/mm
mm
mm
mm
mm
mm
mm
mm
Kg/km
3xl0+lx6
7/Com
7/Com
3.75
2.90
0.7
0.7
0.2
1.8
20.1
740
3x16+1xl0
7/Com
7/Com
4.75
3.75
0.7
0.7
0.2
1.8
22.5
1,004
3x25+2x16
7/Com
7/Com
5.85
4.75
0.9
0.7
0.2
1.8
25.8
1,421
3x35+1x16
7/Com
7/Com
6.90
4.75
0.9
0.7
0.2
1.8
27.7
1,745
3x35+1x25
7/Com
7/Com
6.90
5.85
0.9
0.9
0.2
1.8
28.6
1,864
3x50+lx25
7/Com
7/Com
8.15
5.85
1.0
0.9
0.2
1.8
31.3
2,358
3x50+1x35
7/Com
7/Com
8.15
6.90
1.0
0.9
0.2
1.9
32.0
2.72
3x70+1x35
19/Com
7/Com
9.75
6.90
I.1
0.9
0.2
2.0
35.9
3166
3x70+1x50
19/Com
7/Com
9.75
8.15
I.1
1.0
0.2
2.0
36.8
3.341
3x95+lx50
19/Com
7/Com
11.4
8.15
I.1
1.0
0.5
2.1
41.4
4,611
3x120+1x70
19/Com
19/Com
12.8
9.75
1.2
I.1
0.5
2.3
45.6
5682
3x150+1x95
19/Com
19/Com
14.3
11.4
1.4
I.1
0.5
2.4
50.8
7,072
3x150+1x120
19/Com
19/Com
14.3
12.8
1.4
1.2
0.5
2.5
51.8
7,357
3xI85+1x95
37/Com
19/Com
15.9
11.4
1.6
I.1
0.5
2.6
54.7
8,348
3x185+1x120
37/Com
19/Com
15.9
12.8
1.6
1.2
0.5
2.6
55.8
8638
3x240+1x120
37/Com
19/Com
18.2
12.8
1.7
1.2
0.5
2.7
61.0
10,660
3x240+1x150
37/Com
19/Com
18.2
14.3
1.7
1.4
0.5
2.8
62.2
11024
3x300+1x150
37/Com
19/Com
20.4
14.3
1.8
1.4
0.5
2.9
66.8
12,809
3x300+1xI85
37/Com
37/Com
20.4
15.9
1.8
1.6
0.5
3.0
68.1
13,256
Notes: 1) *All conductors in accordance with lEC 60228. Compact shape (Com.) or non-compact depending on order. 2) Beside above list we can also provide others size depend on customer's requirement.
Electrical PROPERTIES
No. of Core X Cross Section
Conductor
Max.DC resistance of conductor @20°C
Phases
Neutral
Dia.Overall Conducrtor
No./Nominal Diameter of Strands
No./Nominal Diameter of Strands
Pha.
Neu.
Pha.
Neu.
mm2
No/mm
No/mm
mm
mm
Ω/km
Ω/km
3xl0+lx6
7/Com
7/Com
3.75
2.90
1.83
3.08
3x16+1xl0
7/Com
7/Com
4.75
3.75
1.15
1.83
3x25+2x16
7/Com
7/Com
5.85
4.75
0.727
1.15
3x35+1x16
7/Com
7/Com
6.90
4.75
0.524
1.15
3x35+1x25
7/Com
7/Com
6.90
5.85
0.524
0.727
3x50+lx25
7/Com
7/Com
8.15
5.85
0.387
0.727
3x50+1x35
7/Com
7/Com
8.15
6.90
0.387
0.524
3x70+1x35
19/Com
7/Com
9.75
6.90
0268
0.524
3x70+1x50
19/Com
7/Com
9.75
8.15
0268
0.387
3x95+lx50
19/Com
7/Com
11.4
8.15
0.193
0.387
3x120+1x70
19/Com
19/Com
12.8
9.75
0.153
0.268
3x150+1x95
19/Com
19/Com
14.3
11.4
0.124
0.193
3x150+1x120
19/Com
19/Com
14.3
12.8
0.124
0.153
3xI85+1x95
37/Com
19/Com
15.9
11.4
0.0991
0.193
3x185+1x120
37/Com
19/Com
15.9
12.8
0.0991
0.153
3x240+1x120
37/Com
19/Com
18.2
12.8
0.0754
0.153
3x240+1x150
37/Com
19/Com
18.2
14.3
0.0754
0.124
3x300+1x150
37/Com
19/Com
20.4
14.3
0.0601
0.124
3x300+1xI85
37/Com
37/Com
20.4
15.9
0.0601
0.0991
Electrical PROPERTIES Conductor Operating Temperature : 90°C Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor crosssectional area
Reference Method 1 (clipped direct
Reference Method 11 (on a perforated horizontal cable trayor Reference Method 13 [free air] )