300/500V XLPE Insulated, PVC Sheathed, Screened Power Cables (2-4 Cores)
Detail
300/500V XLPE Insulated, PVC Sheathed, Screened Power Cables (2-4 Cores)
FGD200 05ROV-R (CU/XLPE/OSCR/PVC 300/500V Class 2)
APPLICATION The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS Basic design adapted to BS 5308
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)**
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)**
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING 300/500V
CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2. Insulation: Extruded cross-linked XLPE compound. Filler, binder(if any): PP, Mylar tape Circuit Protective Conductor: Annealed plain copper (class 2) Overall Screen: Aluminium/polyester tape Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE Insulation Colour as per BS7671
With Earth Conductor
Without Earth Conductor
2Cores
-
Brown, Blue
3Cores
Yellow/Green, Brown, Blue
Brown, Gray, Black
4Cores
Yellow/Green, Brown, Gray, Black
Brown, Gray, Black, Blue
5Cores
Yellow/Green, Brown, Gray, Black, Blue
Brown, Gray, Black, Blue, Black
Above 5 Cores
Yellow/Green, Black Numbered
Black Numbered
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES Temperature range during operation: Max.90°C for XLPE 250°C in short-circuit for 5secs max. Minimum bending radius: 6 x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor
FGD200 05ROV-R
No. of Core X Cross Section
No./Nominal Diameter of Strands
Nominal Overall Diameter Conductor
Nominal Insulation Thickness
Cross- Section Area Of Circuit Protective Conductor
Nominal Sheath Thickness
Nominal Overall Diameter
Max.Dc Resistance Of Conductor @20°C
Approx. Weight
Noxmm2
No./mm
mm
mm
mm2
mm
mm
Ω/km
kg/km
2x1.0
7/0.44
1.32
0.6
1.0
0.9
8.1
18.1
79
2x1.5
7/0.53
1.59
0.7
1.5
0.9
9.1
12.1
102
2x2.5
7/0.67
2.01
0.8
2.5
1.0
10.5
7.41
146
2x4.0
7I0.85
2.55
0.8
4.0
1.1
11.8
4.61
205
3x1.0
7I0.44
1.32
0.6
1.0
0.9
8.6
18.1
98
3x1.5
7I0.53
1.59
0.7
1.5
0.9
9.6
12.1
129
3x2.5
7I0.67
2.01
0.8
2.5
1.0
11.1
7.41
185
3x4.0
7I0.85
2.55
0.8
4.0
1.1
12.5
4.61
262
4x1.0
7I0.44
132
0.6
1.0
1.0
9.5
18.1
123
4x1.5
7I0.53
1.59
0.7
1.5
1.0
10.6
12.1
162
4x2.5
7I0.67
2.01
0.8
2.5
1.1
12.3
7.41
233
4x4.0
7I0.85
2.55
0.8
4.0
1.2
13.9
4.61
329
Electrical Properties Conductor Operating Temperature : 90°C Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor cross- sectional area
Reference Method 4 (enclosed in conduit in thermally insulating wall etc)
Reference Method 3 (enclosed in conduit on a wall or in trunking etc)
Reference Method 1 (clipped direct)
Reference Method 11 (on a perforated cable tray, horizontal or vertical)
Reference Method 12 (free air)
Horizontal flat spaced
Vertical flat spaced
Trefoil
2 cables, single- phase a.c. or d.c.
3 or 4 cables, 3-phase a.c.
2 cables, single- phase a.c. or d.c
3 or 4 cables, 3-phase a.c.
2 cables, single- phase a.c. or d.c. flat and touching
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or flat and touching
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or 3 c ables three phase
2 cables, single- phase a.c. or d.c. or 3 cables three phase
3 cables, trefoil 3-phase a.c.
1
2
3
4
5
6
7
8
9
10
11
12
mm2
A
A
A
A
A
A
A
A
A
A
A
1.5
18
17
22
19
25
23
-
-
-
-
-
2.5
24
23
30
26
34
31
-
-
-
-
-
4
33
30
40
35
46
41
-
-
-
-
-
Voltage Drop (Per Amp Per Meter)
Nominal Cross Section Area
2 cables d.c.
2 cables, single-phase a.c.
3 or 4 cables, 3-phase a.c.
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)
Ref. Methods 1 and 11 (clipped direct or on trays touching)
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)