450/750V PVC Insulated, Non-sheathed Power Cables (Single Core)
Detail
450/750V PVC Insulated, Non-sheathed Power Cables (Single Core)
FGD100 07V-R (CU/PVC 450/750V Class 2)
APPLICATION The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS Basic design adapted to BS 6491X
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)**
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)**
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING 450/750V
CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2. Insulation: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE Insulation Colour as per BS7671
With Earth Conductor
Without Earth Conductor
2Cores
-
Brown, Blue
3Cores
Yellow/Green, Brown, Blue
Brown, Gray, Black
4Cores
Yellow/Green, Brown, Gray, Black
Brown, Gray, Black, Blue
5Cores
Yellow/Green, Brown, Gray, Black, Blue
Brown, Gray, Black, Blue, Black
Above 5 Cores
Yellow/Green, Black Numbered
Black Numbered
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES Temperature range during operation: Max.90°C 250°C in short-circuit for 5secs max. Minimum bending radius: 6 x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor
FGD100 07V-R
No. of Core X Cross Section
No./Nominal Diameter of Strands
Nominal Insulation Thickness
Nominal Overall Diameter
Approx. Weight
Noxmm2
No./mm
mm
mm
kg/km
1x1.5
7/0.53
0.7
3.1
23
1x2.5
7/0.67
0.8
3.7
35
1x4
7/0.85
0.8
4.3
52
1x6
7/1.04
0.8
4.8
73
1x10
7/1.35
1.0
6.2
120
1x16
7/1.70
1.0
7.2
180
1x25
7/2.24
1.2
9.0
285
1x35
19/1.53
1.2
10.2
375
1x50
19/1.78
1.4
12.0
510
1x70
19/2.14
1.4
14.0
720
1x95
19/2.52
1.6
16.0
995
1x120
37/2.03
1.6
18.0
1230
1x150
37/2.25
1.8
20.0
1520
1x185
37/2.52
2.0
22.0
1900
1x240
61/2.25
2.2
25.0
2480
1x300
61/2.52
2.4
28.0
3100
1x400
61.2.85
2.6
31.5
3950
1x500
61/3.20
2.8
35.0
4950
1x630
127/2.52
2.8
39.0
6360
Electrical Properties Conductor Operating Temperature : 90°C Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor cross- sectional area
Reference Method 4 (enclosed in conduit in thermally insulating wall etc)
Reference Method 3 (enclosed in conduit on a wall or in trunking etc)
Reference Method 1 (clipped direct)
Reference Method 11 (on a perforated cable tray, horizontal or vertical)
Reference Method 12 (free air)
Horizontal flat spaced
Vertical flat spaced
Trefoil
2 cables, single- phase a.c. or d.c.
3 or 4 cables, 3-phase a.c.
2 cables, single- phase a.c. or d.c
3 or 4 cables, 3- phase a.c.
2 cables, single- phase a.c. or d.c. flat and touching
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or flat and touching
3 or 4 cables, 3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or 3 c ables three phase
2 cables, single- phase a.c. or d.c. or 3 cables three phase
3 cables, trefoil 3- phase a.c.
1
2
3
4
5
6
7
8
9
10
11
12
mm2
A
A
A
A
A
A
A
A
A
A
A
1.5
18
17
22
19
25
23
-
-
-
-
-
2.5
24
23
30
26
34
31
-
-
-
-
-
4
33
30
40
35
46
41
-
-
-
-
-
6
43
39
51
45
59
54
-
-
-
-
-
10
58
53
71
63
81
74
-
-
-
-
-
16
76
70
95
85
109
99
-
-
-
-
-
25
100
91
126
111
143
130
158
140
183
163
138
35
125
111
156
138
176
161
195
176
226
203
171
50
149
135
189
168
228
209
293
215
274
246
209
70
189
170
240
214
293
268
308
279
351
318
270
95
228
205
290
259
355
326
375
341
426
389
330
120
263
235
336
299
413
379
436
398
495
453
385
150
300
270
375
328
476
436
505
461
570
524
445
185
341
306
426
370
545
500
579
530
651
600
511
240
400
358
500
433
644
590
686
630
769
711
606
300
459
410
573
493
743
681
794
730
886
824
701
400
-
-
684
584
868
793
915
849
1065
994
820
500
-
-
783
666
990
904
1044
973
1228
1150
936
630
-
-
900
764
1130
1033
1191
1115
1423
1338
1069
Voltage Drop (Per Amp Per Meter)
Nominal Cross Section Area
2 cables d.c.
2 cables, single-phase a.c.
3 or 4 cables, 3-phase a.c.
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)
Ref. Methods 1 and 11 (clipped direct or on trays touching)
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)