450/750V XLPE Insulated, PVC Sheathed Power Cables (2-4 Cores)FGD200 07RV-R (CU/XLPE/PVC 450/750V Class 2)/07RV-R.jpg)
APPLICATION The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. STANDARDS Basic design adapted to IEC 60502-1 FIRE PERFORMANCE Flame Retardance (Single Vertical Wire Test)** | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* | Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)** | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design. VOLTAGE RATING 450/750V CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2. Insulation: Extruded cross-linked XLPE compound. Filler, binder (if any): PP, PET Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request. COLOUR CODE Insulation Colour as per BS7671
| With Earth Conductor | Without Earth Conductor | 2Cores | - | Brown, Blue | 3Cores | Yellow/Green, Brown, Blue | Brown, Gray, Black | 4Cores | Yellow/Green, Brown, Gray, Black | Brown, Gray, Black, Blue | 5Cores | Yellow/Green, Brown, Gray, Black, Blue | Brown, Gray, Black, Blue, Black | Above 5 Cores | Yellow/Green, Black Numbered | Black Numbered |
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES Temperature range during operation: Max.90°C for XLPE 250°C in short-circuit for 5secs max. Minimum bending radius: 6 x Overall Diameter CONSTRUCTION PARAMETERS Conductor | FGD200 07RV-R | No. of Core X Cross Section | No./Nominal Diameter of Strands | Nominal Overall Diameter Conductor | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Max.Dc Resistance Of Conductor @20°C | Approx. Weight | Noxmm2 | No./mm | mm | mm | mm | mm | Ω/km | kg/km | 2x1.0 | 7/0.44 | 1.32 | 0.7 | 1.2 | 8.5 | 18.1 | 101 | 2x1.5 | 7/0.53 | 1.59 | 0.7 | 1.2 | 9.1 | 12.1 | 120 | 2x2.5 | 7/0.67 | 2.01 | 0.7 | 1.2 | 10.0 | 7.41 | 154 | 2x4.0 | 7/0.85 | 2.55 | 0.7 | 1.3 | 11.1 | 4.61 | 205 | 3x1.0 | 7/0.44 | 1.32 | 0.7 | 1.2 | 9.0 | 18.1 | 118 | 3x1.5 | 7/0.53 | 1.59 | 0.7 | 1.2 | 9.6 | 12.1 | 142 | 3x2.5 | 7/0,67 | 2.01 | 0.7 | 1.2 | 10.6 | 7.41 | 185 | 3x4.0 | 7/0.85 | 2.55 | 0.7 | 1.3 | 11.8 | 4.61 | 251 | 4x1.0 | 7/0.44 | 1.32 | 0.7 | 1.2 | 9.8 | 18.1 | 141 | 4x1.5 | 7/0.53 | 1.59 | 0.7 | 1.2 | 10.5 | 12.1 | 171 | 4x2.5 | 7/0.67 | 2.01 | 0.7 | 1.3 | 11.6 | 7.41 | 226 | 4x4.0 | 7/0.85 | 2.55 | 0.7 | 1.3 | 13.0 | 4.61 | 309 |
Electrical Properties Conductor Operating Temperature : 90°C Ambient Temperature : 30°C Current-Carrying Capacities (Amp) Conductor cross- sectional area | Reference Method 4 (enclosed in conduit in thermally insulating wall etc) | Reference Method 3 (enclosed in conduit on a wall or in trunking etc) | Reference Method 1 (clipped direct) | Reference Method 11 (on a perforated cable tray, horizontal or vertical) | Reference Method 12 (free air) | Horizontal flat spaced | Vertical flat spaced | Trefoil |
| 2 cables, single- phase a.c. or d.c. | 3 or 4 cables, 3-phase a.c. | 2 cables, single- phase a.c. or d.c | 3 or 4 cables, 3- phase a.c. | 2 cables, single- phase a.c. or d.c. flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil | 2 cables, single- phase a.c. or d.c. or flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil | 2 cables, single- phase a.c. or d.c. or 3 c ables three phase | 2 cables, single- phase a.c. or d.c. or 3 cables three phase | 3 cables, trefoil 3- phase a.c. | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | mm2 | A | A | A | A | A | A | A | A | A | A | A | 1.0 | 13 | - | - | - | 15 | - | - | - | - | - | - | 1.5 | 18 | 17 | 22 | 19 | 25 | 23 | - | - | - | - | - | 2.5 | 24 | 23 | 30 | 26 | 34 | 31 | - | - | - | - | - | 4 | 33 | 30 | 40 | 35 | 46 | 41 | - | - | - | - | - |
Voltage Drop (Per Amp Per Meter) Nominal Cross Section Area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) | Ref. Methods 1 and 11 (clipped direct or on trays touching) | Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) | Ref. Methods 1, 11 and 12 (in trefoil) | Ref. Methods 1 and 11(Flat and touching) |
|
|
|
|
|
| 1 | 2 | 3 | 4 | 5 | 6 | 7 |
|
|
|
|
|
| mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
|
|
|
|
|
| 1.0 | 46 | 46 | - | - | - | - |
|
|
|
|
|
| 1.5 | 31 | 31 | 27 | 27 | 27 | 27 |
|
|
|
|
|
| 2.5 | 19 | 19 | 16 | 16 | 16 | 16 |
|
|
|
|
|
| 4 | 33 | 12 | 10 | 10 | 10 | 10 |
|
|
|
|
|
|
|