600/1000V PVC Insulated, Non-sheathed Power Cables (Single Core)FGD300 1V-R (CU/PVC 600/1000V Class 2)/1V-R.jpg)
APPLICATION The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. STANDARDS Basic design adapted to BS 6491X FIRE PERFORMANCE Flame Retardance (Single Vertical Wire Test)** | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* | Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)** | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design. VOLTAGE RATING 600/1000V CABLE CONSTRUCTION Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2. Insulation: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request. COLOUR CODE Insulation Colour as per BS7671
| With Earth Conductor | Without Earth Conductor | 2Cores | - | Brown, Blue | 3Cores | Yellow/Green, Brown, Blue | Brown, Gray, Black | 4Cores | Yellow/Green, Brown, Gray, Black | Brown, Gray, Black, Blue | 5Cores | Yellow/Green, Brown, Gray, Black, Blue | Brown, Gray, Black, Blue, Black | Above 5 Cores | Yellow/Green, Black Numbered | Black Numbered |
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES Temperature range during operation: Max.90°C 250°C in short-circuit for 5secs max. Minimum bending radius: 8 x Overall Diameter (unarmoured cable) 10 x Overall Diameter (armoured cable) CONSTRUCTION PARAMETERS Conductor | FGD300 1V-R | No. of Core X Cross Section | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Insulated, Non-Sheathed | Nominal Overall Diameter | Approx. Weight | Noxmm2 | No./mm | mm | mm | kg/km | 1x1.5 | 7/0.53 | 0.7 | 3.1 | 22 | 1x2.5 | 7/0.67 | 0.8 | 3.7 | 34 | 1x4 | 7/0.85 | 0.8 | 4.3 | 50 | 1x6 | 7/1.04 | 0.8 | 4.8 | 70 | 1x10 | 7/1.35 | 1.0 | 6.2 | 116 | 1x16 | 7/1.70 | 1.0 | 7.2 | 174 | 1x25 | 7/2.14 | 1.2 | 9.0 | 276 | 1x35 | 7/2.52 | 1.2 | 10.0 | 366 | 1x50 | 19/1.78 | 1.4 | 11.9 | 502 | 1x70 | 19/2.14 | 1.4 | 13.7 | 706 | 1x95 | 19/2.52 | 1.6 | 16.0 | 974 | 1x120 | 37/2.03 | 1.6 | 17.6 | 1213 | 1x150 | 37/2.25 | 1.8 | 19.6 | 1492 | 1x185 | 37/2.52 | 2.0 | 21.8 | 1868 | 1x240 | 61/2.25 | 2.2 | 24.4 | 2443 | 1x300 | 61/2.52 | 2.4 | 27.7 | 3055 | 1x400 | 61/2.85 | 2.6 | 31.1 | 3888 | 1x500 | 61/3.20 | 2.8 | 34.6 | 4880 | 1x630 | 127/2.52 | 2.8 | 38.6 | 6229 |
Electrical Properties Conductor Operating Temperature : 90°C Ambient Temperature : 30°C Current-Carrying Capacities (Amp) Conductor cross- sectional area | Reference Method 4 (enclosed in conduit in thermally insulating wall etc) | Reference Method 3 (enclosed in conduit on a wall or in trunking etc) | Reference Method 1 (clipped direct) | Reference Method 11 (on a perforated cable tray, horizontal or vertical) | Reference Method 12 (free air) | Horizontal flat spaced | Vertical flat spaced | Trefoil |
| 2 cables, single- phase a.c. or d.c. | 3 or 4 cables, 3-phase a.c. | 2 cables, single- phase a.c. or d.c | 3 or 4 cables, 3-phase a.c. | 2 cables, single- phase a.c. or d.c. flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil | 2 cables, single- phase a.c. or d.c. or flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil | 2 cables, single- phase a.c. or d.c. or 3 c ables three phase | 2 cables, single- phase a.c. or d.c. or 3 cables three phase |
3 cables, trefoil 3-phase a.c. | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | mm2 | A | A | A | A | A | A | A | A | A | A | A | 1.5 | 18 | 17 | 22 | 19 | 25 | 23 | - | - | - | - | - | 2.5 | 24 | 23 | 30 | 26 | 34 | 31 | - | - | - | - | - | 4 | 33 | 30 | 40 | 35 | 46 | 41 | - | - | - | - | - | 6 | 43 | 39 | 51 | 45 | 59 | 54 | - | - | - | - | - | 10 | 58 | 53 | 71 | 63 | 81 | 74 | - | - | - | - | - | 16 | 76 | 70 | 95 | 85 | 109 | 99 | - | - | - | - | - | 25 | 100 | 91 | 126 | 111 | 143 | 130 | 158 | 140 | 183 | 163 | 138 | 35 | 125 | 111 | 156 | 138 | 176 | 161 | 195 | 176 | 226 | 203 | 171 | 50 | 149 | 135 | 189 | 168 | 228 | 209 | 293 | 215 | 274 | 246 | 209 | 70 | 189 | 170 | 240 | 214 | 293 | 268 | 308 | 279 | 351 | 318 | 270 | 95 | 228 | 205 | 290 | 259 | 355 | 326 | 375 | 341 | 426 | 389 | 330 | 120 | 263 | 235 | 336 | 299 | 413 | 379 | 436 | 398 | 495 | 453 | 385 | 150 | 300 | 270 | 375 | 328 | 476 | 436 | 505 | 461 | 570 | 524 | 445 | 185 | 341 | 306 | 426 | 370 | 545 | 500 | 579 | 530 | 651 | 600 | 511 | 240 | 400 | 358 | 500 | 433 | 644 | 590 | 686 | 630 | 769 | 711 | 606 | 300 | 459 | 410 | 573 | 493 | 743 | 681 | 794 | 730 | 886 | 824 | 701 | 400 | - | - | 684 | 584 | 868 | 793 | 915 | 849 | 1065 | 994 | 820 | 500 | - | - | 783 | 666 | 990 | 904 | 1044 | 973 | 1228 | 1150 | 936 | 630 | - | - | 900 | 764 | 1130 | 1033 | 1191 | 1115 | 1423 | 1338 | 1069 |
Voltage Drop (Per Amp Per Meter) Size of conductor | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) | Ref. Methods 1 and 11 (clipped direct or on trays touching) | Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) | Ref. Methods 1, 11 and 12 (in trefoil) | Ref. Methods 1 and 11 (Flat and touching) | 1 | 2 | 3 | 4 | 5 | 6 | 7 | mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | 1.5 | 31 | 31 | 27 | 27 | 27 | 27 | 2.5 | 19 | 19 | 16 | 16 | 16 | 16 | 4 | 33 | 12 | 10 | 10 | 10 | 10 | 6 | 7.8 | 7.9 | 6.8 | 6.8 | 6.8 | 6.8 | 10 | 4.7 | 4.7 | 4.7 | 4 | 4 | 4 | 16 | 2.9 | 2.9 | 2.9 | 2.5 | 2.5 | 2.5 |
|
| r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | 25 | 1.85 | 1.85 | 0.31 | 1.90 | 1.85 | 0.190 | 1.85 | 1.60 | 0.27 | 1.65 | 1.600 | 0.165 | 1.600 | 1.600 | 0.190 | 1.600 | 35 | 1.35 | 1.35 | 0.29 | 1.35 | 1.35 | 0.180 | 1.35 | 1.15 | 0.25 | 1.15 | 1.150 | 0.155 | 1.50 | 1.150 | 0.180 | 1.150 | 50 | 0.99 | 1.00 | 0.29 | 1.05 | 0.99 | 0.180 | 1.00 | 0.87 | 0.25 | 0.90 | 0.860 | 0.155 | 0.870 | 0.860 | 0.180 | 0.870 | 70 | 0.68 | 0.70 | 0.28 | 0.75 | 0.68 | 0.175 | 0.71 | 0.60 | 0.24 | 0.65 | 0.590 | 0.150 | 0.610 | 0.590 | 0.175 | 0.620 | 95 | 0.49 | 0.51 | 0.27 | 0.58 | 0.49 | 0.170 | 0.52 | 0.44 | 0.23 | 0.50 | 0.430 | 0.145 | 0.450 | 0.430 | 0.170 | 0.460 | 120 | 0.39 | 0.41 | 0.26 | 0.48 | 0.39 | 0.165 | 0.43 | 0.35 | 0.23 | 0.42 | 0.340 | 0.140 | 0.370 | 0.340 | 0.165 | 0.380 | 150 | 0.32 | 0.33 | 0.26 | 0.43 | 0.32 | 0.165 | 0.36 | 0.29 | 0.23 | 0.37 | 0.280 | 0.140 | 0.310 | 0.280 | 0.165 | 0.320 | 185 | 0.25 | 0.27 | 0.26 | 0.37 | 0.26 | 0.165 | 0.30 | 0.23 | 0.23 | 0.32 | 0.220 | 0.140 | 0.260 | 0.220 | 0.165 | 0.280 | 240 | 0.19 | 0.21 | 0.26 | 0.33 | 0.20 | 0.160 | 0.25 | 0.185 | 0.22 | 0.29 | 0.170 | 0.140 | 0.220 | 0.170 | 0.165 | 0.240 | 300 | 0.155 | 0.175 | 0.25 | 0.31 | 0.16 | 0.160 | 0.22 | 0.150 | 0.22 | 0.27 | 0.140 | 0.140 | 0.195 | 0.135 | 0.160 | 0.210 | 400 | 0.12 | 0.140 | 0.25 | 0.29 | 0.13 | 0.155 | 0.20 | 0.125 | 0.22 | 0.25 | 0.110 | 0.135 | 0.175 | 0.110 | 0.160 | 0.195 | 500 | 0.093 | 0.120 | 0.25 | 0.28 | 0.105 | 0.155 | 0.185 | 0.100 | 0.22 | 0.24 | 0.090 | 0.135 | 0.160 | 0.088 | 0.160 | 0.180 | 630 | 0.072 | 0.100 | 0.25 | 0.27 | 0.086 | 0.155 | 0.175 | 0.088 | 0.21 | 0.23 | 0.074 | 0.135 | 0.150 | 0.071 | 0.160 | 0.170 |
|