NEK606 Water Blocked P18 RU 0.6/1kV Offshore & Marine Cables
Detail
Applications
These cables are flame retardant, low smoke, halogen freeand mud resistant, used for control, power and lighting systems.
Standards
IEC 60092-353
IEC 60092-351
IEC 60092-359
IEC 60332-1
IEC 60332-3-22
IEC 60754-1,2
IEC 61034-1,2
NEK 606:2004
VG 95218 part 29?
?
Construction
l???? Conductors: Tinned annealed stranded copper to IEC 60228 class 2. l???? Insulation: Halogen-free EPR. l???? Filler: Water blocking fillers, if required l???? Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness. l???? Inner Sheath: Halogen free thermosetting compound, SHF2, coloured black. l???? Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional, but can not meet low smoke standard.
Electrical Characteristics
Nominal Cross Section Area
mm2
1.5
2.5
4
6
10
16
25
35
Nominal Conductor Diameter
mm
1.6
2.1
2.6
3.2
4
5.1
6.5
7.4
Maximum DC Resistant@20?
O/km
12.2
7.56
4.7
3.11
1.84
1.16
0.734
0.529
Continuous Current Rating@45?1 Core
A
23
30
40
52
72
96
127
157
Continuous Current Rating@45?2 Core
A
20
26
34
44
61
82
108
133
Continuous Current Rating@45?3&4 Core
A
16
21
28
36
50
67
89
110
Short Circuit Current 1s
A
210
360
570
860
1430
2290
3580
5010
Operating Voltage
KV
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
Nominal Cross Section Area
mm2
50
70
95
120
150
185
240
300
Nominal Conductor Diameter
mm
8.7
10.3
12.2
13.8
15.1
17.0
19.6
21.9
Maximum DC Resistant@20?
O/km
0.391
0.27
0.195
0.154
0.126
0.1
0.0762
0.0607
Continuous Current Rating@45?1 Core
A
196
242
293
339
389
444
522
601
Continuous Current Rating@45?2 Core
A
167
206
249
288
331
444
444
511
Continuous Current Rating@45?3&4 Core
A
137
169
205
237
272
311
365
421
Short Circuit Current 1s
A
7150
10020
13590
17170
21460
26470
34340
42930
Operating Voltage
KV
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN=I1/ 3v N ), I1= Current rating for 1-core, N = Number of cores.